Valve Short Description

Connection Ends Flange to BS EN 1092-2:1997
Temperature Range 0℃ – 80℃
Coating Fusion Bonded Epoxy Coating in accordance with ANSI/AWWA C550
Working Pressure PN10 / PN16

Ask a Question
Guarantee Safe & Secure Checkout
  • Free delivery over 00
  • 30 Days Return Period
Categories: ,

Description

Deluge Alarm Valve

Statement SK790X Deluge Alarm Valve is a diaphragm type of hydraulic control valve driven by the hydraulic pressure
within the piping system. It functions as a flow control and alarming device in sprinkler and pre-action systems,
starting the sprinkler system for fire suppression and triggering fire alarms when fire is detected.
Operational Principle Equipped with solenoid, anti-reset controller, mini strainer, ball valves, and pressure gauges.

Set Condition: Ball valve (3) open; valves (7), (8), (9) closed; anti-reset controller connected; gauges (1) & (6) show same value.
Work Condition: Triggered by opening solenoid valve (8), ball valve (7), or remote valve (9), releasing pressure and opening the valve for water flow, alarm, and signal transmission.

Properties & Advantages
  • Automatic operation using pipe system pressure (energy saving & eco-friendly).
  • Controlled by pilot valve with low energy consumption & stable pressure reducing.
  • Dual cavity design for smooth operation without pressure fluctuation.
  • Straight-flow channel minimizes friction, cavitation, vibration, and noise.
  • High durability with ductile iron castings, stainless steel, copper alloys, and DuPont rubber.
  • Fusion bonded epoxy coating (ANSI/AWWA C550) for superior corrosion resistance.
Notes for Installation & Debugging
  • Check pressure switch & alarm bell before installation to avoid leaks.
  • Ensure anti-reset controller is sealed and functional before pressurizing.
  • Adjust ball valves to ensure the valve is in set condition before use.
Common Problems & Solutions Problem: Water leakage after pressing anti-reset controller.
Solutions:

  • Check sealing surfaces of valve or controller for damage/sundries.
  • Check diaphragm condition.
  • Ensure valves (7), (8), (9) are fully closed.

Problem: No water discharge when opening valves (7), (8), (9).
Solutions:

  • Check if valves (7), (8), (9) are actually opened.
  • Inspect stem of basic valve for blockage and repair if needed.

 

There are no reviews yet.

Be the first to review “Remote Float Control Valve SK790X Deluge Alarm Valve”

Your email address will not be published. Required fields are marked *

Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • SKU
  • Rating
  • Price
  • Stock
  • Availability
  • Add to cart
  • Description
  • Content
  • Weight
  • Dimensions
  • Additional information
Click outside to hide the comparison bar
Compare
shopping cart close